Monoblock Burners

NG Series Gas - Heavy Oil Burners

ECO 9 K(S) C 3a NG

  • Easy maintenance with hinged system without dismounting the burner from the boiler,
  • Sliding flange for connection to different boiler types,
  • Lower noise level with special muffler system,
  • Early diminishing of error sources thanks to the plug-socket connection that allows minimizing the number of cable connections,
  • Combustion cap adjustable to desired capacity,
  • High combustion efficiency by providing optimum fuel-air mixture with fuel-air servo motors that can be adjusted with high precision,
  • High performance fan,
  • User-friendly operator panel,
  • Specially-designed, compact pre-heater, safety, operation and limiting thermostat,
  • Optional CO/O2 (trim) system integration for combustion optimization,
  • Adequate gas supply control with minimum gas pressurestat.
  • Combustion air control with air pressurestat,
  • High pressure mechanical atomization at nozzle,
  • Leak control with integrated gas leak controller,
  • Pilot ignition
Burner Type Natural Gas
Capacity
Natural Gas
Capacity
Natural Gas
Consumption
Fuel-Oil
Capacity
Fuel-Oil
Capacity
Fuel-Oil
Consumption
Fan Motor Power Fuel Pump Power Fuel
Heater
Voltage at 50 Hz
Min. kcal/h Max. kcal/h Min. kW Max. kW Min. Nm³/h Max. Nm³/h Min. kcal/h Max. kcal/h Min. kW Max. kW Min. kg/h Max. kg/h kW kW kW VAC
ECO 9 K(S) C 3a NG 774.000 7.740.000 900 9000 93,8 938,2 1.083.600 7.774.000 1260 9000 112,3 802,1 22 4 37 3N 400
 * L Gmin Gmax H K B C ØP M ØD ØD1
ECO 9 K S C 3a NG 2110     - 375 1450 750 2030 1055 22 450 508    -

*All dimensions in mm.

SPECIFICATIONS ECO 9 K S C 3a NG
Control Type O
Mechanical Proportional (Liquid fuel control)
Pneumatic Proportional (21mbar) (Gas fuel control)
Pneumatic Proportional (300 mbar) (Gas fuel control)
Electronic Proportional (21mbar)
Electronic Proportional (300 mbar)
Air flow setting SM
Fuel flow adjustment SM
Gas Valve
Pilot ignition
Pilot Gas Valve
Minimum gas pressure
Maximum gas processore
Gas Leak Control
Air processor
Flame Control F
Liquid fuel heating and pumping station
Liquid fuel hoses
Hinged body for service purposes
Different flame tube length
O2-CO combustion management system connection
Combustion air fan inverter connection
Fuel preparation stations (Gas line / Diesel Station)
TSE EN-676 Burners-Compatibility for Gas Fuels
CE declaration of conformity
Electrical protection class IP54

: Not Included / N/A

: Optional

: Included / Available

1K: Single Stage

2K: Two Stage

O: Modulating

M: Manuel

SM: Servomotor

İO: Ionization

F: Photocell

DA: Direct Ignition

PA: Pilot Ignition